Duct System Design Quick Reference Guide
The Duct System Design Quick Reference Guide is a concise technical resource that outlines best practices, standards, and calculation methods for designing efficient, code-compliant air distribution systems in HVAC applications. It supports engineers and designers in selecting appropriate duct sizes, configurations, materials, and accessories to ensure proper airflow, pressure balance, thermal performance, and energy efficiency. The guide synthesizes ASHRAE, SMACNA, and ACCA guidelines into actionable design criteria.
π Overview
π Key Components
π― Applications
- β Commercial Office HVAC Systems
- β Healthcare Facility Air Handling Units
- β Residential Forced-Air Distribution Networks
π Key Formulas
Airflow Requirement
CFM = (Sensible Load Γ 1.08) / (T_room β T_supply)
Calculates required airflow (CFM) based on sensible cooling load and temperature difference between room and supply air.
Friction Loss
ΞP = R Γ L
Estimates pressure drop (in. w.g.) where R is friction rate (in. w.g./100 ft) and L is duct length (ft); derived from the Darcy-Weisbach or Hazen-Williams analogs adapted for ducts.
Equivalent Diameter (Rectangular Duct)
D_e = 1.30 Γ (a Γ b)^0.625 / (a + b)^0.25
Converts rectangular duct dimensions (a, b in inches) to equivalent circular diameter for friction loss calculations.