Psychrometric Analysis Quick Reference Guide
The Psychrometric Analysis Quick Reference Guide is a concise technical resource that summarizes essential properties, relationships, and calculations for moist air using the psychrometric chart and fundamental thermodynamic principles. It enables engineers and technicians to rapidly determine air state points—including dry-bulb temperature, wet-bulb temperature, humidity ratio, relative humidity, dew point, and enthalpy—under varying atmospheric conditions. The guide serves as a practical tool for HVAC system design, energy analysis, and indoor environmental quality assessment.
📖 Overview
📑 Key Components
🎯 Applications
- ✓ HVAC system sizing and energy modeling
- ✓ Indoor air quality (IAQ) monitoring and control
- ✓ Industrial drying and moisture-sensitive manufacturing processes
- ✓ Building envelope condensation risk analysis
- ✓ Thermal comfort evaluation (e.g., PMV/PPD modeling)
📐 Key Formulas
Humidity Ratio (ω)
ω = 0.622 × (P_v / (P_t − P_v))
Calculates the mass of water vapor per kilogram of dry air, where P_v is partial pressure of water vapor and P_t is total atmospheric pressure.
Relative Humidity (φ)
φ = P_v / P_{vs}
Ratio of actual water vapor pressure to saturation vapor pressure at the same dry-bulb temperature; expressed as a percentage.
Specific Enthalpy (h)
h = c_{pa} × T_db + ω × (h_{fg} + c_{pv} × T_db)
Total energy content per kilogram of dry air, combining sensible heat of dry air and latent + sensible heat of water vapor.
Dew Point Temperature (T_dp)
Solve for T where P_{vs}(T) = P_v
Temperature at which moist air becomes saturated upon cooling at constant pressure; determined iteratively or via Magnus-type empirical equations.